| GENERAL INFORMATION The SENTINEL VACUUM CONTROLLER is a
diaphragm operated pneumatic valve. With proper
installation, it is capable of maintaining a stable vacuum
with +- (plus/minus) .2" Hg. over an adjustable range of
10'' - 15" Hg. at the regulator.
The SENTINEL VACUUM CONTROLLER has been
designed to correct several serious faults inherent in other
types of regulators.
1. The SENTINEL is not load sensitive. It
may be adjusted to a desired vacuum level with or without
the milking units on the line. This is particularly valuable
to the dairyman who milks with a varying number of units. As
each unit is removed or added to the system, the Sentinel
will automatically compensate for the changing load. In
areas where testing devices are used, no readjustment is
necessary to correct for the additional load of the units on
the pipeline. However, it cannot offset the pressure drop
which occurs in the claw due to the weigh device being in
series with the milk hose on each unit.
2. The SENTINEL has a fully open to a fully
closed span of .2" Hg. This means that when the vacuum rises
or falls more than .2'' Hg. the regulator will open to
maximum or close. It is not unusual to see most weight type
regulators still admitting air into the system although the
vacuum level has fallen 2 or more inches.
3. The SENTINEL will return to its set-point
within .l" after a drop in vacuum level caused by a leak
into the system.
4. The SENTINEL is easy to adjust. It may be
set within .l" Hg of the desired level with a special wrench
supplied with each regulator. This key is designed to
prevent unauthorized personnel from changing the vacuum
level, without the owner's consent.
5. SENTINEL VACUUM CONTROLLERS never
completely shut off, therefore, a small amount of air is
always passing through the unit, even when the poppet is in
the closed position. The reason for this air pass-by is
because of the .003 clearance
between the poppet and the body of the unit. This clearance
is necessary to minimize friction, thereby allowing
instantaneous reaction to changes in vacuum levels. The
amount of air that passes by the poppet is called air
pass-by and amounts to approximately 10 CFM in the Model
100, 15 CFM in the Model 350 and 25 CFM in the Model 500.
6. Filter gauges (standard with models 500,
350 and 100, part #348-12) indicate the condition of vacuum
controller filters. When the button on the filter gauge
pulls in flush with the face, the filter should be changed
for dependable operation.
OPERATING PRINCIPLE
(Refer to Figure #1)
As vacuum is applied on first system start
up, a vacuum is drawn on the bottom side of the diaphragm
(348-9), through the main sensing port located in the bottom
of the poppet shaft. The regulator is biased at
approximately 3.0" Hg. via the spring (348-3). The vacuum is
drawn into the dome (348-11) through the hole in the
diaphragm. Once the desired set point is reached, the
bellows assembly (348-35) admits air into the dome through
dome filter assembly (348-36) and felt filter (348-15),
passing through the regulating seat in bellows assembly into
the dome (348-11) thus maintaining a constant vacuum in the
dome. This vacuum is 3.0'' Hg. below the regulating point of
the controller. EXAMPLE: Controller set at I0'' Hg, thus
giving 13.0'' Hg. regulating point. At this point the
diaphragm is in a balanced condition. Any rise in vacuum
will move the diaphragm (348-09) in a downward direction
thus opening the valve wider. Any drop will move the
diaphragm toward the dome, causing the valve to close. Since
the resistance of the moving assembly is very low, a fully
open to fully closed range of ± .2” Hg may be obtained.
Figure #1
MOUNTING INSTRUCTIONS
1. The SENTINEL VACUUM CONTROLLER should be
mounted at approximately eye level for maximum ease of
periodic servicing (changing filters when required). Avoid,
whenever possible, mounting close to hot water heaters and
vacuum pumps, especially in small engine rooms or confined
areas with poor ventilation.
2. Install as close to sanitary trap as
possible if maximum control is desired. A tee with an
automatic drain on the bottom should be provided to insure
drainage after wash-up.
3. Avoid mounting on reserve tanks or
headers whenever possible. In some cases this can result in
a pipe-organ effect and cause an oscillation or pulsing
problem. If this is encountered, a double elbow or offset
may be necessary to break up direct airflow beneath the
regulator. In some cases placement in a different location
may be required. For best results mount the Model 100
with a 2" elbow below it and mount the Model 350 and Model
500 with a 3" elbow below it. For example, when mounting
a Model 350 on a 4" vertical line, first place a 4" to 3"
conversion T in the line, then come out with 6 to 12 inches
of 3" pipe, then place a 3" - 90 degree elbow, add
approximately 3 to 6 inches of 3 inch line upwards, place
the inlet adapter, then attach the bottom of the Model 350
with the quick disconnect clamp to the inlet adapter.
If you are mounting a
Model 350 or Model 500 on a horizontal line between two
receiver groups, place a T similar as above, on its side, in
the middle of the line separating the two receiver groups.
Then add a 6" piece of horizontal pipe, then place a 3"
elbow pointing upwards, then add 3 inches of 3" pipe and
then add the inlet adapter.
4. It is not necessary to use a pipe wrench
to tighten the regulator to the line. A small amount of pipe
dope or Teflon tape should be used before installation to
provide a seal and prevent galling.
5. Do not reduce the pipe-size the regulator
is mounted on to a size less than the diameter of the
regulator base, unless the entire system's pipe size is
smaller in diameter than the diameter of the regulator base.
EXAMPLE: On the model 100, do not reduce below 1 1/2" NPT.
6. At no time should any type lubricant be
applied to the regulator (especially WD40). Such lubrication
will only cause a collection of foreign particles,
restricting movement and eventually destroying the silicone
rubber diaphragm.
7. At the time of installation, the customer
should be instructed in the adjustment and filter
replacement procedure. If the customer is not under a
regular service program with his dealer, he should be shown
the procedure for cleaning and routine care.
8. Adjustment of desired vacuum level is
simply made with the special steel wrench provided with each
regulator. Follow these steps: (A) Remove the snap-on top
dome filter. (B) Looking down from the top, insert the
adjusting wrench in the center of the piece on the top of
the dome. (C) Clockwise rotation of the adjusting screw will
raise the level, counter clockwise will lower the setting.
9. Upon initial starting of the vacuum pump,
the regulator will open fully and then gradually begin to
close until its set-point is reached. It is recommended that
all drains and valves be closed before system start-up. If
too many leaks into the system are permitted and the pump
cannot pull at least 8" Hg., the regulator may remain open.
The filter gauge provided on Models 500, 350 and 100 has a
black button an its face. This button will pull in flush
when it is time to change filters. The regulator will
automatically correct for filter restrictions of up to 30"
H20. But beyond this point sufficient air cannot be taken in
to keep vacuum levels down to the desired point.
10. The filter retaining
ring must be checked periodically to insure a firm seal. New
filters tend to take a cold set and become loose. If this
occurs, dirt and foreign particles will by-pass it and
become lodged on the moving parts. This may cause sluggish
or erratic regulation. It is recommended that each time the
filter is changed, the bottom half of the unit below the
flange (348-08 Model 350/500, 353-02 Model 100) be washed
out with warm water solution of mild liquid household
detergent. (DO NOT USE PIPELINE SOAP OR OTHER POWDERS HAVING
CAUSTIC COMPOUNDS IN THEM.)
11. If frequent filter
change is encountered a large filter adapter kit is
available (348-13 Models 350/500 and 353-13 Model 100).
Also, the Peacekeepers for each model provide larger
filters.
12. Relief Valves (348-17
and RV-463) are offered as optional equipment. They should
be mounted between the pump and the vacuum controller.
Relief Valves are factory set but should be reset on any
given system because sizes of systems will vary. Settings
can be adjusted to a higher vacuum by turning the screw
clockwise and lower by turning the screw counter-clockwise.
The adjustment screw is located in the center of the
threaded end of the Relief Valves. Further instructions
regarding placement and setting are available in an
instruction sheet accompanying the valves.
Manuals here on the web are a work in process. We are adding
pages so that eventually the complete manuals will reside
here. Please check back, soon. Thank you!
|